30 796689 (4188-658) i2_04/07
To enable or disable
alarm sounders
The alarm sounders of the system can be
manually disabled, for example when doing
maintenance work on the sounder circuit. On
completion of maintenance work the alarms
must be re-enabled.
Enter access level 2 (A2) and use the
navigation buttons to highlight and
select options:
Press to toggle selection
between:
ENABLED (Default)
DISABLED
Select
A2
mi n
A2
Press to select field [ ]
Previous Next
Press to select field [ ]
Previous Next
Press to select field [ ]
Previous Next
[Status]
1
2
3
P1
EEPR
O
M
enable
1
2
3
P1
EEPROM
enable