T775R SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0249—13 12
IMPORTANT
1. This action sets the maximum setpoint value of 
all outputs to the setpoint high limit maximum.
2. Setting the high limit setpoint maximum is 
irreversible. If you perform the action 
inadvertently and this setpoint adversely affects 
the control of your system, you must replace the 
controller.
Programming the T775R 
Controller
To program the controller, select one of the following 
procedures depending on whether the Reset function is to 
be used:
• Program Outputs for Reset — See “1. Programming 
Outputs (Relay and Mod) with Reset” on page 12
• Program Outputs for No Reset — Refer to 
“2. Programming Outputs (Relay and Mod) with No 
Reset” on page 16
When programming is complete, you may continue with 
“4. Scheduling” on page 31 or, for advanced options, 
continue with “3. Setup (Advanced Options)” on page 19.
1. PROGRAMMING OUTPUTS 
(RELAY AND MOD) WITH 
RESET
The T775R can be programmed for Reset or No Reset for 
each output. From the factory, the T775R is programmed 
for No Reset. This section describes the steps necessary 
to program the controller for Reset.
To use the Reset feature, the first output (MOD 1 or Relay 
1 depending on the model) must be set to Reset=YES in 
Setup mode (See “1.1. Setting Up the Controller for 
Reset”). 
The reset curve established when programming the first 
output (MOD 1) is then used for all subsequent outputs 
that are configured for Reset, and each of those outputs 
will be offset from this curve. 
For all outputs that will follow a reset curve, be sure to 
configure for Reset=YES in the setup mode. Choose 
Reset YES or NO for all other outputs you wish to reset, 
then press the HOME button to record your selection.
If using the time clock or DI to go to setback, 
the T775R will shift the reset curve up or down 
and cause the controlled setpoint to exceed 
either the entered reset max. temp or min. 
temp (dropping below reset minimum is most 
common, since setback is normally below 
setpoint). If this is not desired, either do not 
use setback, or adjust the min. and max. 
values entered so that critical setpoints are 
not exceeded in the setback mode.
Fig. 24. Reset Setup.
1.1. Setting Up the Controller for Reset
1. Press and hold the MENU button for five seconds to 
enter Setup mode. 
2. Then choose:
OUTPUTS 
RELAY 1 (or MOD1 if Mod outputs present) 
RESET 
then select YES -BOILER or YES-OTHER.
You can now press the HOME button to exit Setup mode 
and continue with “Determining and Setting the Reset 
Values”.
Determining and Setting the Reset 
Values
NOTE: When using the Reset feature, Sensor A must 
be sensing the controlled temperature (e.g. 
Boiler), Sensor B must be sensing the reset-
ting temperature (e.g. outdoor temp).
To program an output for Reset, refer to the values as 
shown in the examples below and in Fig. 25 on page 13. 
Choose your own appropriate values for Sensor A 
maximum and minimum and Sensor B maximum and 
minimum. 
Reset Example: (Refer to Fig. 25 on page 13)
• Sensor A is the boiler sensor and Sensor B is the 
outdoor sensor.
• Maximum boiler temperature desired is 210°F (99°C) 
when the outdoor temperature is 20°F (-7°C).
• Minimum boiler temperature desired is 160°F (71°C) 
when the outdoor temperature is 70°F (21°C).
• With the above settings example, when the outdoor 
temperature is 50°F (10°C), the effective setpoint is 
180°F (82°C).
Setback (optional) Example: (Refer to Fig. 25 
on page 13)
• Setback of -10°F (-12°C) is used to drop the 
temperature at night by 10°F (-12°C).
• With the above settings example, when the outdoor 
temperature is 50°F (10°C), the effective setback 
setpoint is 170°F (77°C) (180°F (82°C) setpoint minus 
the 10°F (-12°C) setback). 
NOTES:
SETUP
 OUTPUTS
 RELAY 1 (or MOD1)
 RESET
SETUP
OUTPUTS
RELAY 1
RESET
USE
RESET
FOR
RELAY 1
YES-BOILER
YES-OTHER
NO
M24303