T775R SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0249—13 6
See Figures 8 through 18 for typical T775R wiring 
applications.
Fig. 7. T775R Terminal and Feature Locations.
NOTE: Refer to Table 1 on page 1 for the specific 
configuration of sensors and outputs 
supported by the model you are installing.
a
For Series 90 connections, you must insert a 340 Ohm 
resistor across terminals R and W (Refer to Fig. 17 on 
page 8). The resistor is included with the controller. 
b
A separate earth ground is required for all installations 
regardless of the power source (24, 120, or 240 Vac).
WIRING APPLICATION 
EXAMPLES
Figures 8 through 18 illustrate typical controller wiring for 
various applications.
NOTE: For wiring examples of Series 90, M9184 or 
M9185 Modutrol Motors, refer to the T775A/B/
M Series 2000 Electronic Stand-alone Con-
trollers Installation Instructions (form 62-
0254).
NOTE: The Electronic Series 90 output provided 
with modulating T775 models cannot drive 
electromechanical slidewire devices like 
older Series 3 mod motors (prior to series 6), 
V9055s, and S984s.
Fig. 8. Wiring for Two-Stage Control – 24 Vac Input 
and 24 Vac Load.
Table 2. Description of Wiring 
Terminal Connections.
Connection Terminal Label Description
Sensors
Sensor A T T Temperature Sensor; 
polarity insensitive
Sensor B
Outputs
Relay 1
Relay 2
Relay 3
Relay 4
NO
COM
NC
120-240 Vac Relay 
Output
Mod 1 + - (Vdc or mA)
W R B (Series 90)
a
Modulating Output
Mod 2
Input
DI  + - Digital Input (dry 
contact)
24 Vac Power
24V +  + 24 Vac Hot
Common  C 24 Vac Common
Ground
Earth Ground
b
C
NO
NC
C
NO
NC
C
NC
NO
C
NC
NO
T  
T
T  
T
B
R
W
+
 
–
+
 
–
B
R
W
+
 
–
SENSOR A
SENSOR B
MOD 2
MOD 1
KNOCKOUT A
DIGITAL
INPUT
POWER 
120/240 VAC
OUTPUT
RELAY 2
KNOCKOUT D
POWER
24 VAC
OUTPUT
RELAY 1
KNOCKOUT C
KNOCKOUT E
SENSORS  A AND B USE THE TWO TT CONNECTIONS AND ARE 
POLARITY INSENSITIVE.
FOR MOD 1 AND MOD 2 CURRENT (mA) OR VOLTAGE (VDC) OUTPUT, 
USE SIGNAL (+) & COMMON (-).
FOR MOD 1 AND MOD 2 SERIES 90 OUTPUT, USE W, R, & B.
A SEPARATE EARTH GROUND IS REQUIRED FOR ANY POWER
SOURCE (24, 120, OR 240 VAC).
1
2
1
2
M24284
OUTPUT
RELAY 3
KNOCKOUT B
OUTPUT
RELAY 4
3
3
C
+
120
COM
240
120 or 240 Vac Power
120 Vac 120 120 Vac Power
Common COM Common
240 Vac 240 240 Vac Power
Table 2. Description of Wiring 
Terminal Connections. (Continued)
Connection Terminal Label Description
L1
(HOT)
L2
24 VAC
COM
NO
COM
NO
M24285A
LOAD 2
LOAD 1
C
NO
NC
C
NO
NC
C
+
SENSOR A
SENSOR B
T  
T 
T  
T