T775R SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
31 62-0249—13
Fig. 78. Setup - Outputs - Relay - Reset Runtime.
3.3.6.4. RESET RT (run time)
This selection displays only if “Show RT = YES” is 
selected during Output Options setup (Refer to “3.3.5.4. 
SHOW RT (show run time hours)” on page 27).
1. Press the  button to display the Reset RT values.
2. Use the  and  buttons to select YES or NO.
Default: NO
3. Press the  button to accept the value and return to 
the Relay menu.
Selecting YES immediately resets the output run time 
hours to zero for this output. When you subsequently 
return to this screen, the RESET RT defaults to NO.
NOTE: Run times can be reset to zero for each 
individual relay. You must do this for each 
relay that you want to reset to zero.
3.3.7. Setup the Next Relay
To setup the next relay output go to “3.3.6. Setting up the 
Relays” on page 28.
3.4. Exiting Setup
Press the  button to exit the selected relay set up and 
return to the Outputs menu.
If you are finished setting up the relay outputs, press the 
HOME button to exit Setup mode and return to the home 
screen display.
This completes the Setup procedure. 
4. SCHEDULING
Scheduling provides the ability to set daily temperature 
settings for up to two events per day. Typically, these are 
the daytime (setpoint) and the nighttime (setback) 
settings.
IMPORTANT
To enable Scheduling, you must first enter Setup 
mode (press and hold the MENU button for 5 
seconds), select OUTPUTS, select OPTIONS, 
select USE SCHED, and then select YES. (Refer 
to “3.3.5.1. USE SCHED” on page 26).
IMPORTANT
To properly account for Daylight Saving time, be 
sure to set the Date before setting the Time. 
Refer to “4.2.2. SET DATE” on page 33.
NOTE: The T775R controller interface is intuitive. 
You may find that you do not need the follow-
ing scheduling instructions. You may want to 
use this procedure simply as a reference to 
locate the particular option or parameter of 
interest.
NOTE: Each output is independently configurable to 
follow the schedule or not. For modulating 
outputs, Refer to “3.3.3.1.5. SCHEDULE” on 
page 24. For relay outputs, Refer to “3.3.6.2. 
SCHEDULE” on page 30.
NOTES:
1. If you press the HOME button or there is no 
keypad activity for four minutes, you exit 
Scheduling mode and return to the home 
screen.
2. If you press the MENU button, you exit 
Scheduling mode and return to the menu.
To create or change a schedule, you use the — 
• Left arrow button () to scroll backward through the 
Schedule menus
• Right arrow button () to select the highlighted menu 
item and display its content
• Up and Down arrow buttons ( and ) to scroll up 
and down through a list of items or to increase or 
decrease the value of a displayed schedule parameter
SETUP
 OUTPUTS
 RELAY 1
 RESET RT
SETUP
OUTPUTS
RELAY 1
RESET RT
RESET
RUN TIME
FOR
RELAY 1
YES
NO
M24357