T775R SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0249—13 30
Fig. 75. Setup - Outputs - Floating Relay - Derivative.
3.3.6.1.1.3. DERIVATIV (modulating/floating 
relay only)
The Derivative option displays only on the T775R2001 
and the T775R2035 models when the Type option = 
Floating.
1. From the menu, use the  and  buttons to high-
light DERIVATIV.
2. Press the  button to display the actuator value.
3. Use the  and  buttons to increase/decrease the 
desired number of seconds.
Default: 0 seconds
Range: 0 to 3,600 seconds)
4. Press the  button to accept the value and display 
the SCHEDULE option.
Continue with “3.3.6.2. SCHEDULE” for the remaining 
relay selections.
Fig. 76. Setup - Outputs - Relay - Schedule.
3.3.6.2. SCHEDULE
This selection displays only if “Use Sched = YES” is 
selected during the Output Options setup (Refer to “3.3.5. 
OPTIONS” on page 26). When selected, individual 
outputs default to follow the schedule.
1. Press the  button to display the Schedule values.
2. Use the  and  buttons to select YES or NO.
Default: YES
3. Press the  button to accept the value and return to 
the Relay menu.
An individual output can be selected to be controlled or 
not controlled by the schedule.
If NO is selected, the Setback selection does not appear 
in the Program menu for this output.
Fig. 77. Setup - Outputs - Relay - Reset.
3.3.6.3. RESET
The Reset menu displayed (Fig. 77) depends on whether 
the controller has modulating outputs:
• For controllers with modulating outputs, the first output 
(MOD 1) is settable for Reset, which then enables 
Reset to be set for the Relay outputs. Refer to 
“3.3.3.1.6. RESET” on page 25.
• For controllers with no modulating outputs, this 
selection enables the controller’s Reset function, and 
allows each relay output to be individually programmed 
for Reset or No Reset.
IMPORTANT
To use the Reset function of the controller, the 
first output (MOD 1 or Relay 1 depending on the 
model) must be set for Reset.
1. Press the  button to display the Reset values.
2. Use the  and  buttons to select YES or NO.
Default: NO
3. Press the  button to accept the value and return to 
the Relay menu.
• If you select YES, then all other outputs display this 
Setup option and will use the reset curve programmed 
for the first output.
• If you select NO, then No Reset is configured for that 
output and all other subsequent outputs. 
SETUP
  OUTPUTS
 FLOAT 1
   DERIVATIV
ENTER
DERIVATIVE
TIME FOR
FLOAT 1
SETUP
OUTPUTS
FLOAT 1
DERIVATIV
0
SEC
M24354
SETUP
 OUTPUTS
 RELAY 1
 SCHEDULE
SETUP
OUTPUTS
RELAY 1
SCHEDULE
USE
SCHEDULE
FOR
OUTPUTS
YES
NO
M24355
SETUP
OUTPUTS
RELAY 1
RESET
USE
RESET
FOR
RELAY 1
YES
NO
SETUP
OUTPUTS
RELAY 1
RESET
USE
RESET
FOR
RELAY 1
YES-BOILER
YES-OTHER
NO
CONTROLLERS WITH MODULATING OUTPUTS
CONTROLLERS WITH NO MODULATING OUTPUTS
SETUP
 OUTPUTS
 RELAY 1
 RESET
SETUP
 OUTPUTS
 RELAY 1
 RESET
M24356