T775R SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0249—13 24
NOTES:
a. The Integral time is factory set for 400 seconds and is 
similar to the response time to the T775J Series 1000 
models. This is a good middle range and should 
satisfy many applications. The integral time can be 
increased for applications where sensed response is 
slow, and can be decreased for applications where 
sensed response is fast (e.g. discharge air control).
b. As a starting point, an optimal integral time for 
discharge air typically ranges from 12 to 200 
seconds. An optimal integral time for room control 
typically ranges from 60 to 2,500 seconds. The 
purpose of integral action is to reduce or eliminate 
the offset from setpoint during steady state control 
that is often seen in proportional only control.
c. Keep in mind that control is most sensitive to 
throttling range. Adjust the throttling range first before 
any adjustment to integral time. Adjust throttling 
range to be as wide as possible to start since this will 
provide the most stable control. Remember that the 
integral will eliminate the steady state error so you do 
not need to have a small throttling range to have 
accurate control. (Integral action allows for controlling 
to a setpoint even with a wide throttling range).
Fig. 59. Setup - Outputs - Mod Out - Derivative.
3.3.3.1.4. DERIVATIVE
The Derivative default value is factory set to zero (no 
derivative control). It is strongly recommended that the 
derivative remain at zero (0) unless you have a very good 
reason to adjust it. Derivative control is not needed in the 
vast majority of HVAC applications.
1. From the Mod menu, use the  and  buttons to 
highlight DERIVATIV.
2. Press the  button to display the Derivative sec-
onds.
3. Use the  and  buttons to increase/decrease the 
value.
Default: 0 (zero)
Range: 0 to 3,600 seconds
4. Press the  button to accept the seconds and 
return to the Mod menu.
Fig. 60. Setup - Outputs - Mod Out - Schedule.
3.3.3.1.5. SCHEDULE
The Schedule option displays only if the USE SCHED 
parameter is set to Yes (Refer to Fig. 65 on page 26).
1. From the Mod menu, use the  and  buttons to 
highlight SCHEDULE.
2. Use the  and  buttons to highlight YES or NO.
Default: YES
3. Press the  button to accept the selection and 
return to the Mod menu.
Each output can be set up to follow or ignore the built in 
scheduler. To disable the scheduler for all outputs, Refer 
to “3.3.5.1. USE SCHED” on page 26.
SETUP
  OUTPUTS
 MOD 1
   DERIVATIV
ENTER
DERIVATIVE
TIME FOR
MOD 1
SETUP
OUTPUTS
MOD 1
DERIVATIV
0
SEC
M24338
SETUP
 OUTPUTS
  MOD 1
 SCHEDULE
SETUP
OUTPUTS
MOD 1
SCHEDULE
USE
SCHEDULE
FOR
OUTPUTS
YES
NO
M24339