T775R SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0249—13 26
Fig. 64. Setup - Outputs - Options Menu.
3.3.5. OPTIONS
1. From the Outputs menu, use the and  buttons 
to highlight OPTIONS. 
2. Press the  button to display the Options menu.
Fig. 65. Setup - Outputs - Options - Schedule.
3.3.5.1. USE SCHED
1. Press the  button to display the schedule selec-
tions.
2. Use the and  buttons to highlight YES or NO.
Default: NO
3. Press the  button to accept the value and display 
the MIN OFF option.
Selecting NO disables scheduling for all outputs.
Selecting YES enables scheduling for the setpoint. 
However, each individual output can be removed from 
scheduling as desired. 
With Scheduling enabled, when you return to Program 
mode, the new option for Scheduling displays. You can 
press the HOME button and then the MENU button to 
view the Schedule options in the menu.
Refer to “3.3.3.1.5. SCHEDULE” on page 24.
Fig. 66. Setup - Outputs - Options - Min Off/On Time.
3.3.5.2. MIN OFF or MIN ON
This is the minimum number of seconds of “off time” or 
“on time” for all relays.
1. Press the  button to display the Min Off/On value.
2. Use the  and  buttons to increase/decrease the 
desired number of seconds from 0 to 990 seconds 
in 10 second increments.
Default: 0 (zero)
Range: 0 to 990 seconds
3. Press the  button to accept the seconds and dis-
play the DI OPTIONS.
NOTES:
a. The minimum off time applies to all relay outputs
b. When minimum off time is active, relays waiting to be 
energized display a flashing square underneath the 
relay number on the home screen.
c. If the minimum off time is not equal to zero (0), the 
minimum off time activates at power-up. 
d. To manually override, press the  button at any time.
SETUP
 
OUTPUTS
  OPTIONS
SETUP
OUTPUTS
OPTIONS
USE SCHED
MIN OFF
MIN ON
DI OPTS
SHOW RT
SYNC
EXIT
M24343A
SETUP
 OUTPUTS
 OPTIONS
 USE SCHED
SETUP
OUTPUTS
OPTIONS
USE SCHED
USE
SCHEDULE
FOR
OUTPUTS
YES
NO
M24344
     SETUP
 OUTPUTS
  OPTIONS
 
ENTER
MINIMUM
OFF TIME
FOR RELAYS
SETUP
OUTPUTS
OPTIONS
MIN OFF
0
SEC
M24535A
OR
MIN ON
ENTER
MINIMUM
ON TIME
FOR RELAYS
SETUP
OUTPUTS
OPTIONS
MIN ON
0
SEC
MIN OFF