LCN System Installation 9-1 9/96
9
UNIVERSAL STATION
X
INSTALLATION
Section 9
Provides for the installation of the Universal Station
X
station available in Release 410 or later
systems.
9.1 PLACEMENT
The Universal Station
X
can
be placed in any existing console as if it were a Universal
Station node. The same complexing instructions apply as if it were a US.
This applies to Universal Station
X
in Standard Furniture and in Ergonomic Furniture.
9.2 GROUNDING
The Universal Station
X
is grounded the same as a Universal Station with the logic ground
connected to the chassis ground (safety ground).
9.3 POWER
The Universal Station
X
has the following power consumption:
Table 9-1 — Universal Station
X
Current
Power Specifications
Avg RMS True RMS Peak Watts BTUs/hr
2.04 4.2 10.6 332 1132
9.4 LCN CABLE CONNECTION
The LCN A and LCN B cables are connected as any other node in the system—see
Section 3.
9.5 ETHERNET NETWORK CONNECTION
The Media Access Unit (MAU) is mounted on the end of the 2 meter adapter cable
(Cabletron p/n 9300011-2M). The other end of this cable is connected to J6 on the WSI
I/O board in slot 2.
The MAU is connected to a Local Area Network (LAN) using BNC cable. The adapter
cable is necessary to avoid interference with the LCN A cable connection.