LCN System Installation 10-5 9/96
10.4
10.4 INSTALLATION IN A CONSOLE Global User Station
UCN Taps can be placed in the bottom of a Global User Station if a NIM is located in the
same station cabinet.
Follow this procedure to install taps in a Universal Station in Ergonomic Furniture.
Step Action
1
Mount a tap to each mounting bracket.
Isolated port marker must be located on right side of the mounting
bracket.
Mount the tap with a bolt through the hole in the tap.
ATTENTION
Do not mount with the grounding stud.
Tighten the mounting bolt to only 25 inch pounds—just enough
to hold the tap fixed in place.
ATTENTION
Do not crush the body of the tap.
2
Connect a 14 AWG/2.5 mm
2
ground wire from each tap directly to the
nearest safety ground.
Do not daisy-chain the connection.
3 Connect a drop cable, 51195153-XXX (XXX is the length in meters),
to each drop cable connection 1.
It is very important to tighten the drop cable connectors to 25 inch
pounds to ensure an error-free UCN system.
4 Connect the other end of the drop cables to the NIM Modem card.
ATTENTION
Pay strict attention to connecting the drop cable from
Cable A to the Cable A connection on the Modem card and the drop
cable from Cable B to the Cable B connection on the Modem card.
5 Install the rest of the UCN Cable System as shown in the publication
UN20-100 that is found in the bag of taps. The same instructions are
found in Appendix A of
UCN Guidelines
.

Table of Contents