LCN System Installation 16-4 9/96
16.7
The mounting of the LCN MAU is done in the bottom, front side of the station. The UCN
tap and LCN MAU are located side-by-side under the access plate as shown below.
16365
Figure 16-4 — Mounting of an LCN MAU with no UCN Taps
The coax cables and T-connectors required were installed during the preparation phase of
the installation. Observe the cable in use display. Immediately after a cable switch, pick
the inactive cable and connect its coax T-connector to the appropriate MAU connector for
that cable. Then, after the next cable switch to the other cable, connect the other coax
T-connector.
– Connect the A cable T to the A cable connector on the MAU.
– Connect the B cable T to the B cable connector on the MAU.