Specifications
I/O Module Configuration
96 UMC800 Controller Installation and User Guide Release F
4/01
Component Parameter Description
Pulse/Frequency Inputs
with Digital Outputs
Input 1 to 4
Voltage Levels
Logic Input High Vih: 3.0 Vdc
Logic Input Low Vil: 1.0 Vdc
Absolute Max: 27 Vdc
Absolute Min: 0.0 Vdc
Digital Output
(Open Collector
Circuit)
Max On DC Impedance: 330 ohms
Min Off DC Impedance: >10 Mohms
Max Source Voltage: 27 Vdc
Min Load DC Impedance: 0 ohms
Frequency Mode
Limitations
Frequency Min: 10 Hz frequency mode
Frequency Max: 100 kHz frequency mode
Min Frequency Duty Cycle @ 100 kHz: 10 %
Max Frequency Duty Cycle @ 100 kHz: 90 %
Pulse Mode Limitations Pulse Width Min: 100 uSec
Pulse Width Max: unlimited
Outputs per Module
6
Relay (Alarm) Outputs
(Module ID 6)
Contact Rating
4 A, 250 Vac on resistive load
Contact Type
SPST normally closed (NC), individually configurable to
normally open (NO) via jumper
Time Resolution
4 msec.
Module
Any Digital Output may be configured.
Time Proportional
Outputs (TPO)
Synchronization
Individual TPOs are not synchronized with others.
*Base Power Required is the power required to provided module operation within specifications.