EasyManua.ls Logo

Honeywell UMC800 - I;O module limits

Honeywell UMC800
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mounting and Wiring
Plug-in Module Locations
20 UMC800 Controller Installation and User Guide Release F
4/01
I/O module limits
The controller backplane accommodates I/O module types, subject to the limitations as shown in Table 7.
Slot Locations identify the allowable locations in the controller for each I/O module type. Maximum
Allowed describes the maximum I/O configuration for each I/O type in a controller.
Table 7 I/O module installation limitations
I/O Module Type Slot Locations
(See Figure 9)
Maximum Allowed
Universal Analog Input (ID: 1) 1 through 16 16 modules (64 points)
Analog Output (ID: 2) 1 through 10 4 modules (16 points)
Digital Input (ID: 3,4,5) 1 through 16 16 modules (96 points)*
Digital Input 16 point (ID: B) 14 through 16 3 modules (48 points)*
Digital Output (ID: 6,7,8) 1 through 8 8 modules (48 points)*
Digital Output (ID: A) 9 through 16 2 modules (12 points)*
± 15 Vdc pH Power Module (ID: C) 5, 6 2 modules (8 points)
Pulse/Frequency Input (ID: D) 1 through 16 16 modules (64 points)
NOTE: Total combined I/O of all types is limited by the 16 available controller I/O slots.
* Total of 96 DI/DOs allowed for all types combined.