EasyManua.ls Logo

Honeywell UMC800 - Field wiring for one pH sensor input (module ID C)

Honeywell UMC800
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mounting and Wiring
Signal Wiring
26 UMC800 Controller Installation and User Guide Release F
4/01
Field wiring for one pH sensor input (module ID C)
Figure 14 indicates the recommended wiring for one pH sensor input. Note that two analog input channels
are required, one for the pH sensor and one for temperature. Similar wiring may be used for additional
sensors. A UMC800 controller can accommodate 2 power modules for a total of up to 8 pH inputs.
1
12
1
12
1
C
Analog Input
Module
+
COM
-
pH 1 Sensor
mV
pH 1 Sensor
Temp
+
-
C
-
-
C
+
+
+
-
+
C
-
Mod 1
Mod 4
Green
Black
Blue
White/Black
(Unused)
Orange
Red/Black
Red
White
Jumper
UMC800 Shield Connector Kit
Part No. 51309814-501
Power Supply Module
UMC800 Controller
Figure 14 Recommended wiring for one pH sensor input