EasyManua.ls Logo

Honeywell UMC800 - Controller status LEDs; Diagnostic displays

Honeywell UMC800
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maintenance
Replacement Procedures
72 UMC800 Controller Installation and User Guide Release F
4/01
Replacing the power supply fuse
The power supply input circuit is protected with a fuse. Use the steps in the table below to replace the fuse
on the power supply module.
Step Action
1 Remove power from the controller.
2
Locate the fuse holder located on the power supply module. See Figure 36.
3
Using a slotted screwdriver, remove the fuseholder cap by rotating it counterclockwise.
4
Replace the fuse with the proper size and type.
For 100-240 V supply: Size 5x20, F 3.15 A Time Delay 250 V, or equivalent.
For 24 V supply: Size 5x20, 6.3 A Slow Blow, or equivalent.
5
Replace the cap by pressing in and rotating it clockwise with the screwdriver.
_
100 - 240 V ~
50 / 60 Hz
100 VA MAX.
F 3,15 A T
250V
L1
L2 / N
CPU Battery
Location
Fuse Holder
POWER
LoBAT
FORCE
RUN
DIS
PLAY
BAT
COMM B COMM A
Replace battery with Tadi ra
n TL5101/S
on
ly
. Us e of ano
th
er
ba
t
te
ry may
prese
nt
a risk of fire or ex
plosi
on.
See use
rs
g
ui
de for i
nstructions
.
Power
Supply
CPU
Module
Figure 36 Power supply fuse and CPU battery location

Table of Contents

Other manuals for Honeywell UMC800

Related product manuals