EasyManua.ls Logo

Honeywell UMC800 - Environmental and Operating Conditions

Honeywell UMC800
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications
Environmental and Operating Conditions
Release F UMC800 Controller Installation and User Guide 99
4/01
Environmental and Operating Conditions
Parameter Reference Rated Extreme Transportation
and Storage
Ambient Temp.
°F
°C
77 ± 5
25 ± 3
32 to 131
0 to 55
32 to 140
0 to 60
40 to 151
40 to 66
Ambient Relative
Humidity *
10 % to 55 % RH
non-condensing
10 % to 90 % RH
non-condensing
5 % to 90 % RH
non-condensing
5 % to 95 % RH
non-condensing
Mechanical
Acceleration
Duration
0 g
0 ms
1 g
30 ms
5 g
30 ms
20 g
30 ms
Vibration
10 Hz to 60 Hz
amplitude 0.07 mm
(peak-to-peak)
0 Hz to 14 Hzamplitude
2.5 mm (peak-to-peak)
60 Hz to 150 Hz
acceleration 1 g
14 Hz to 250 Hz
acceleration 1 g
*Relative Humidity is derated above 40 °C.