Specifications
PV Inputs
Release F UMC800 Controller Installation and User Guide 101
4/01
Range Standard
°F °C
RTD/Ohms
Pt 100 at 0 °C
130 to 464
58 to 302
32 to 212**
32 to 392
32 to 752
328 to 1472
90 to 240
50 to 150
0 to 100**
0 to 200
0 to 400
200 to 800
IEC 751-1986
IEC 751-1986
IEC 751-1986
IEC 751-1986
IEC 751-1986
IEC 751-1986
Ni 50 ohms
112 to 608 80 to 320 Edison #2045A-1962
Ni 508 ohms
112 to 302 80 to 150
Cu 10 ohms
4 to 482** 20 to 250** General Electric
Ohms
0 to 200 ohms
0 to 2000 ohms
JIS
58 to 302
32 to 212**
32 to 392
32 to 752
328 to 932
50 to 150
0 to 100**
0 to 200
0 to 400
200 to 500
JIS C 1604-1981
JIS C 1604-1981
JIS C 1604-1981
JIS C 1604-1981
JIS C 1604-1981
Linear
Milliamperes
0 to 20 mA*
4 to 20 mA*
Millivolts
0 to 10 mV
10 to 10 mV
0 to 20 mV
20 to 20 mV
0 to 50 mV
50 to 50 mV
10 to 50 mV
0 to 100 mV
100 to 100 mV
0 to 500 mV
500 to 500 mV
Volts
0to1 V
1to1 V
0to2 V
2to2 V
0to5 V
5to5 V
1to5 V
0 to 10 V
10 to 10 V
Carbon
Oxygen
0 to 1250 mV
30 to 510 mV
*mA inputs must be connected with a 250 ohm resistor across the input terminals.
**These ranges have an accuracy of 0.25 %.