Mounting and Wiring
Remote Access
Release F UMC800 Controller Installation and User Guide 49
4/01
Best Data 56SX Data Fax External Modem
Step Action
1
Connect the modem to a PC. If your PCs RS232 port has a 2- pin connector, use a DB-9 male
to DB-25 female modem cable. If your PCs RS232 port has a 9-pin connector, use a DB-9
male to DB-9 female RS232 cable.
2
Connect power to the modem.
3
Power-up the modem.
4
Run a serial communication port program such as Hyperterminal.
5
Within the communication program, select the port to which the modem is connected.
6
Configure the port to these settings:
baud rate = 9600
data bits = 8
parity = none
stop bits = 1
flow control = none
7
In the programs terminal window, type in the letters AT E1 Q0 followed by the enter key. The
modem should give an OK response.
8
Enter the following command string:
AT &C0 &D0 &K0 &R1 &S0 &Y0 S0=1
Modem should respond with OK.
9
Enter the following command string:
AT E0 Q1 &W0
Modem will not respond.
10
Power down the modem and disconnect it from the PC.
11
Connect the modems serial cable to the RS232 port of the UMC800 using a DB-9 male to
DB-9 male RS232 cable. Null modem cable may not work.
12
Connect the modem to a telephone jack.
13
Power up the modem and the UMC800.
14
On a remote computer, run Control Builder software.
15
Set up Control Builder to dial the UMC800.
16
Verify that communications is established with the remote UMC800.