VisionPRO TM 8000 Touchscreen Programmable Thermostat
Table 3. Installer Setup Menu. (Continued)
Installer Setup
Number
0260
O27O
Installer Setup Name
Cycles per hour (cph) for
3rd Stage Heat
(Aux Heat for 3H/2C
Heat Pumps)
Cycles per hour (cph) for
Em Heat
Settings
1--1 cph used for steam and gravity
3--3 cph for hot water systems and high efficiency (90%
or better) furnaces
5--5 cph for standard fossil fuel forced air (less than 90%
efficient) systems (factory setting)
9--9 cph used for electric furnaces or electric auxiliary
heat for heat pump systems
2, 4, 6, 7, 8, 10, 11, 12--other cycle rate settings
3--3 cph for hot water systems and high efficiency (90%
or better) furnaces
5--5 cph for standard fossil fuel forced air (less than 90%
efficient or better) systems
9--9 cph for electric strip heat for heat pumps
0--Backlight not on continuously. Thermostat backlight
comes on with each key press.
l--Backlight is on continuously (thermostat must have a
common wire attached for this function).
Notes
Only shown if 3H/2C
heat pump is selected.
Only shown if 2H/1C or
3H/2C heat pump is
selected.
0280 Continuous Backlight Option is always shown;
however, continuously on
backlight works only if
thermostat is wired with
24 Vac Common.
0300 Changeover
0310 Deadband Shown only if automatic
changeover is selected.
0--manual changeover (factory setting)
l--auto changeover
Heating and cooling setpoints can be set no closer than
chosen value:
2--2°F (1.5°C)
3--3°F (2°C)
4--4°F (2.5°C)
5--5°F (3°C)
6--6°F (3.5°C)
7--7°F (4°C)
8--8°F (4.5°C)
9--9°F (5°C)
0--fahrenheit temperature display (factory setting)
l--celsius temperature display
0320 Temperature Indication
Scale
0330 Daylight Savings 1--daylight savings is on (factory setting).
0--daylight savings is off.
0340
0350
0--no remote temperature sensor
l--outdoor temperature sensor for displayonly.
2--outdoor temperature sensor for control. Outdoor
sensor used for Heat Pump Lockout settings. (See Heat
Pump Temperature Lockout section for more details.)
3--indoor temperature sensor
0--no compressor lockout.
Remote Temperature
Sensor (Outdoor or
Indoor)
Heat Pump Compressor
Set to 0 in areas that do
not follow daylight
savings.
Defaults and Options
depend on System Type
selection.
indoor Temperature
Sensor uses an averaging
network and does not
include on-board sensor.
Default depends on other
Lockout or (Balance
Point)
15°F(-9.5°C)
20°F (-6.5°C)
25°F (-4°C)
30°F (-1 °C)
35°F (1.5°C)
40°F (4.5°C)
45°F (7°C)
selections. Shown if
Outdoor Temperature for
control is selected. (See
Advanced Features
section for more
information.)