EasyManua.ls Logo

Honeywell VisionPRO 8000 - Installer System Test; How to Use the Installer System Test

Honeywell VisionPRO 8000
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VisionPRO TM 8000 Touchscreen Programmable Thermostat
INSTALLERSYSTEMTEST
Use the Installer System Test to test the heating, cooling and
fan (and emergency heat for heat pump systems).
\ CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed during
Installer System Test
Avoid cycling compressor quickly.
Howto Usethe InstallerSystemTest
The installer Test is part of the Installer Setup Menu.
1. Enter the Installer System Test by entering the installer
Setup.
2. Note that the test appears at the end of the Installer
Setup Numbers.
3. See Fig. 30 to review how the thermostat buttons are
used during the installer System Test. See Table 6 for
available Installer System Tests.
NUMBER
-SYSTEM STATUS - UP ARROW
NUMBER TURNS THE
SYSTEM ON
DONE KEY- UP ARROW
EXFSINSTALLER ADVANCES TO
SYSTEM TEST NEXT SYSTEM
TESTNUMBER
DOWN ARROW
TURNS THE
SYSTEM OFF
M22428
Fig. 30. Review thermostat buttons used during Installer
System Test.
Installer System Tests
IMPORTANT
Use the Installer System Test to test the heating, cooling, fan and emergency heat. The setting you choose for System
Type (Installer Setup Number 0170) may prevent some System Test Numbers from appearing.
Table 4. Installer System Test.
System Test Number Test Type System Status Number and Description
Test I Cooling System Test 1--Cool stage 1 turns on.
2--Cool stage 1 and stage 2 turn on.
0--Cool is off.
Test 2 Fan System Test 1--Fan turns on.
0--Fan turns off.
Test 3 Heating System Test 1--Heat stage 1 turns on.
2--Heat stage 1 and stage 2 (aux heat) turn
on.
0--Heat is off.
Test 4 Emergency Heat Test 1--Emergency heat turns on.
2--Emergency heat and auxiliary heat turn on.
0--Emergency heat turns off.
Press the Next button to go to the beginning of the Installer Setup or press the Done button to exit the Installer
System Test.
68-0280 20