Installation  20 
 
 
 
Connecting the REPO port 
 
 
WARNING: The pins on the REPO port are polarity sensitive. Be sure to verify polarity while 
connecting the REPO port. 
 
 
 
WARNING: To meet the requirements stated in NEC (NFPA 70) Articles 645-10 and 645-11, 
a UPS installed in a computer equipment room must be connected to a REPO circuit. 
 
 
 
IMPORTANT: The remote switch must be in the Off (open) position to enable power to the 
output receptacles.