UPS operations  30 
 
 
NOTE: Configure mode times out after 2 minutes of inactivity. If the Test/Alarm Reset button 
has not been pressed, any new selections are not saved. 
 
For the location of buttons, see "UPS front panel controls (on page 7)." 
For the location of LEDs, see "UPS front panel LED indicators (on page 8)." 
 
Available voltage settings 
 
  NOTE: An asterisk (*) indicates the default setting. 
 
  
UPS model  Available settings utility voltage (VAC) 
Associated LED ("UPS 
front panel LED 
indicators" on page 8) 
R3000 NA  100  General Alarm 
 
110  On Battery 
 
120*  Battery Fault 
 
127  Site Wiring Fault 
R3000j JPN  100*  General Alarm 
 
110  On Battery 
 
120  Battery Fault 
 
127  Site Wiring Fault 
R3000h NA, R3000h JPN  200/208*  General Alarm 
 
220  On Battery 
 
230  Battery Fault 
 
240  Site Wiring Fault 
R3000 INT  200/208  General Alarm 
 
220  On Battery 
 
230*  Battery Fault 
 
240  Site Wiring Fault 
 
 
Initiating a self-test 
To initiate a self-test, press and hold the Test/Alarm Reset button ("UPS front panel controls" on page 7) 
for three seconds. 
Because a portion of the self-test requires battery power, the self-test cannot be initiated if the batteries are 
less than 90 percent charged. If the UPS detects a problem, the appropriate LED ("UPS front panel LED 
indicators" on page 8) illuminates and an audible alarm may sound. 
For information on what to do if the self-test detects a problem, see "Troubleshooting (on page 41)."