EasyManua.ls Logo

HP J4367A - UPS R3000 XR - Troubleshooting; LED and Audible Alarm Troubleshooting

HP J4367A - UPS R3000 XR
65 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting 41
Troubleshooting
LED and audible alarm troubleshooting
Genera
l Alarm
LED
On
Batter
y LED
Batter
y Fault
LED
Site
Wiring
Fault
LED
Utility
LED
Overloa
d LED
Audible
alarm
Can
alarm be
silenced
("Silencin
g an
audible
alarm"
on page
31)?
Condition
Off Off Off Off Green Off
No audible
alarm
N/A
UPS is in Operate
mode (on page 27)
Off Off Off Off
Flashin
g
green
Off
No audible
alarm
N/A
UPS is in Standby
mode (on page 27)
Off Off Off Off Red Off
On1 beep
every 5
seconds
Yes
UPS is in Auto-Bypass
mode (on page 28)
Flashing
red
Off Off Off Red Off
On1 beep
every 5
seconds
Yes
General alarm
conditionUPS is in
Auto-Bypass mode
("General alarm
condition" on page
42)
Off Off Off Off
Flashin
g red
Off
On1 beep
every 5
seconds
Yes
Bypass is out of range
(on page 43)
Off Off
Flashin
g red
Off Off Off
On1 beep
every 5
seconds
Yes
Battery test failure
("Battery condition"
on page 43)
Off
Flashin
g red
Off Off Off Off
On1 beep
every 5
seconds
No
Low battery (no utility
power) ("UPS is on
battery" on page 43)
Off Off
Flashin
g red
Off Off Off
On1 beep
every 5
seconds
Yes
Batteries are
disconnected ("Battery
condition" on page
43)
Off Red Off Off Off Off
On1 beep
every 5
seconds
Yes
On batteryNo utility
power ("UPS is on
battery" on page 43)

Table of Contents

Other manuals for HP J4367A - UPS R3000 XR

Related product manuals