HP ProLiant DL380 Generation 3 Server High-Density Deployment
18
High-Voltage
Y-Cables
The Vertical-Mount PDU Bracket with High-Voltage Cables kit includes 11 Y-cables, each of which is
3.0 m (10 ft) long. The single-cord PDU section is 1.8 m (6 ft) long, and the dual-cord server section
is 1.3 m (4 ft) long. Refer to Table 9 for part numbers.
Note: You do not need the vertical-mount PDU bracket to mount any of the PDUs listed in Table 9.
However, the Y-cables shipped with the Vertical-Mount PDU Bracket kit may be still be used if needed.
Y-cables have a single-cord section with an IEC connector that connects to the PDU, a dividing joint
in the center, and a dual-cord section with IEC connectors that connect to the servers. One Y-cable
supplies power from the PDU to two servers in the standard configuration or one server in the
maximum configuration.
CAUTION: When installing server power cords into the PDUs, ensure that the load is balanced
among the output circuit breakers. Do not exceed the ratings of the circuit breakers.
Table 9. High-Voltage Power Cables
Description HP Part # Description
Vertical-Mount PDU Bracket with High-
voltage Cables kit
166097-B21
This kit includes two sets of PDU brackets and 11 Y-
cables. Each cable is 3.0 m (10 ft) long with a 1.8-m
(6-ft) section on the single-side and 1.2-m (4-ft) sections
on the dual-side.
142257-001
(1.8 m/6 ft)
142257-002
(2.4 m/8 ft)
142257-003
(3.0 m/10 ft)
142257-006
(1.4 m/4.5ft)
10A IEC-to-IEC Cables kit
142257-007
(1.4 m/4.5 ft), 15
cables
The IEC-to-IEC cables can be used either as individual
power cords to connect PDUs or to extend the length of
the high-voltage Y-cables. The server ships with one
3.0-m (10-ft) IEC-to-IEC cable, part number
142263-003.
Power Cords
The server ships with an IEC-to-IEC power cord (PN 142263-003) used for rack mounting with high-
voltage PDUs. For low-voltage, stand-alone deployments or installation without a rack, country-
specific power cord options are available.
U.S. and Japanese models ship with two power cords—IEC-to-IEC and a country-specific cord:
• Power cord, US, IEC320-C13 to IEC320-C14, 10 A 250 V, Straight (3 m/10 ft)
(PN 142257-002)
• Power cord, US, IEC320-C13 to NEMA 5–15P, 15 A 125 V, Straight (3 m/10 ft)
(PN 103541-001)
The power cord included with the North American model of the server can be used for low-voltage
applications. Use a 1.8-m (6-ft) to 2.4-m (8-ft) long power cord with the standard rack rails and cable
management arm.
For information on obtaining high-voltage power cords, visit the HP website:
www.hp.com/products/ups