EasyManua.ls Logo

HP ProLiant DL380 - Server Component Identification

HP ProLiant DL380
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HP ProLiant DL380 Generation 3 Server High-Density Deployment
9
Table 3. ProLiant DL380 Generation 3 Server Parameters continued
Rack Rails and Hardware Weights
Cable arm 0.81 kg (1.8 lb)
Slide (2) 2.07 kg (4.6 lb)
Rail (2) 1.8 kg (4.0 lb)
Total Weight 4.7 kg (10.4 lb)
Power Ratings
Maximum Power Supply Rated Input AC Power
115 V 565 W
240 V 540 W
Maximum System Measured Input AC Power
115 V 458 W
240 V 434 W
Maximum Power Supply Rated Input Current
115 V 4.9 A
240 V 2.3 A
Maximum System Measured Input Current
115 V 4.1 A
240 V 1.8 A
System Thermal Dissipation (per hour)
115 V 1,560 BTUs
240 V 1,481 BTUs
Relative Humidity (non-condensing)
Operating 10 to 90%
Non-operating 5 to 95%

Other manuals for HP ProLiant DL380