UPS operations 34
1. Initiate a REPO by closing the REPO contact.
CAUTION: If the polarity is reversed while connecting the REPO port, the UPS powers up
normally.
2. Verify proper connection of the REPO port:
a. Power up the UPS by pressing the Power button.
b. Disconnect the REPO port.
c. Reconnect the REPO port.
If the polarity is correct, the REPO connectors can be disconnected, and then reconnected, without
initiating a REPO.
d. Verify that the UPS remains in Operate mode (on page 31).
e. If a REPO is initiated, the polarity is reversed. Check and correct the connections.
Powering down the UPS
1. Shut down all load devices.
2. Switch the load segment circuit breakers the OFF position.
3. Press and hold the Power button for 3 seconds. Power is removed from the load segments and the
ON/OFF button blinks.

Table of Contents

Other manuals for HP R5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP R5000 and is the answer not in the manual?

HP R5000 Specifications

General IconGeneral
Output Voltage230V
Form FactorRack-mountable
Rack Height3U
Nominal Output Voltage230V
TopologyDouble Conversion Online
Input Voltage230V
Frequency50/60 Hz
Battery Recharge Time3 hours
Transfer Time0 ms
Operating Temperature0 - 40 °C
Battery TypeSealed Lead Acid (SLA)
InterfaceUSB, Serial
Output Power Capacity4500 Watts
Efficiency95%
Power Capacity5000 VA
Dimensions43.2 x 66 x 13 cm