Component identification 9
Item Description
1
ERM connector for the small plug on the split ERM cable
2
Load segment 1 circuit breaker (controls the C19 and C13
receptacles, but does not control the large output
receptacle)
3
Load segment 1 (two IEC-320-C19 receptacles and two
IEC-320-C13 receptacles)
4
Cord retention clip attachment locations
5
Load segment 2 (two IEC-320-C19 receptacles and two
IEC-320-C13 receptacles)
6
REPO port
7
USB communications port
8
Serial communications port
9
HP UPS Network Module
10
Ground bonding screw
11
Input power line cord with NEMA L6-30 plug (NA/JPN) or
IEC-309-32A plug (INTL)
12
Load segment 2 circuit breaker
13
Large output NEMA L6-30R receptacle (NA/JPN) or
IEC-309-32A receptacle (INTL) associated with load
segment 1
14
ERM connector for the large plug on the split ERM cable
REPO port
The UPS includes an isolated REPO port. When properly wired, the REPO feature enables the power at the
UPS output receptacles to be switched off from a remote location. To use this feature, the REPO port must be
connected to a remote, normally open switch (not supplied). The REPO switch is used in conjunction with a
main disconnect device that removes the AC source from the input of the UPS. When the switch is closed:
The REPO feature immediately powers down protected devices and does not utilize the orderly
shutdown procedure initiated by power management software.
The REPO feature shuts down UPS units operating under either utility or battery power.
NOTE: If the UPS was operating on battery power when the remote switch was closed, no power
is available to the load devices until utility power is restored and the UPS has been manually
powered up.
To restore power to the load devices after the REPO feature is activated, press the On button after the AC
source is reconnected to the UPS.
IMPORTANT: Pressing and holding the On button without utility present normally initiates a
battery start and the UPS assumes the load. However, if the On button is pressed and a REPO is
detected, battery start is inhibited and the UPS is not able to assume the load. The electronics
module fan spins and the General Alarm LED and an audible alarm are active as long as the On
button is held.
To power down the entire network in the event of an emergency, the REPO ports of multiple UPS units can be
connected to a single switch.

Table of Contents

Other manuals for HP R5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP R5000 and is the answer not in the manual?

HP R5000 Specifications

General IconGeneral
Output Voltage230V
Form FactorRack-mountable
Rack Height3U
Nominal Output Voltage230V
TopologyDouble Conversion Online
Input Voltage230V
Frequency50/60 Hz
Battery Recharge Time3 hours
Transfer Time0 ms
Operating Temperature0 - 40 °C
Battery TypeSealed Lead Acid (SLA)
InterfaceUSB, Serial
Output Power Capacity4500 Watts
Efficiency95%
Power Capacity5000 VA
Dimensions43.2 x 66 x 13 cm