Troubleshooting 47
a. Power down the UPS ("Powering down the UPS" on page 34).
b. Remove one or more load devices to reduce the power requirements.
c. Wait at least 5 seconds and restart the UPS.
d. If the condition persists, verify that the load devices are not defective.
4. Allow the UPS to cool:
a. Power down the UPS ("Powering down the UPS" on page 34).
b. Clear vents and remove any heat sources.
c. Verify that the airflow around the UPS is not restricted.
5. Wait at least 5 minutes and restart the UPS.
6. If the condition persists, contact an HP authorized service representative.
Input voltage is out of range
Action:
1. Check the input voltage and reconfigure the UPS ("Configuring the UPS" on page 32).
2. Contact a qualified electrician to verify that the utility power is suitable for the UPS.
Insufficient warning of low batteries
Action:
1. Verify that the power management software is not delaying the shutdown of attached servers when the
UPS is in a low battery condition.
2. Allow the UPS batteries to charge for 48 hours.
3. If a Battery Fault occurs, replace the batteries.
Internal UPS fault condition
Action:
1. Power down the UPS ("Powering down the UPS" on page 34).
2. If the condition persists, contact an HP authorized service representative.
Low battery shutdowns
Possible cause::Ungraceful shutdown of attached servers occurs when the UPS is in a low battery condition.
Action:
1. Verify that the power management software is not delaying the shutdown of attached servers when the
UPS is in a low battery condition.
2. Allow the UPS batteries to charge for 48 hours.
3. If a Battery Fault occurs, replace the batteries.

Table of Contents

Other manuals for HP R5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP R5000 and is the answer not in the manual?

HP R5000 Specifications

General IconGeneral
Output Voltage230V
Form FactorRack-mountable
Rack Height3U
Nominal Output Voltage230V
TopologyDouble Conversion Online
Input Voltage230V
Frequency50/60 Hz
Battery Recharge Time3 hours
Transfer Time0 ms
Operating Temperature0 - 40 °C
Battery TypeSealed Lead Acid (SLA)
InterfaceUSB, Serial
Output Power Capacity4500 Watts
Efficiency95%
Power Capacity5000 VA
Dimensions43.2 x 66 x 13 cm