Troubleshooting  45 
Alarm number  Alarm name  Alarm description  Alarm type 
59 
Utility Not Present  The utility level has fallen below the Utility Not Present 
threshold.   
Notice 
68 
Battery DC Over Voltage   Battery voltage levels have exceeded the maximum 
allowable limits. 
Alarm 
94 
To Bypass Command  A request to transfer to Manual Bypass Mode 
received from software. 
Event 
95 
From Bypass Command  A request to transfer to Operate Mode is received 
from software. 
Event 
143 
On Manual Bypass  The UPS is manually commanded to switch to bypass 
and will remain in bypass until commanded out of 
bypass. 
Notice 
149 
Service Battery  A faulted battery string is detected, and the battery 
charger has been disabled until it is replaced.  
Alarm 
159 
Output Overload Level 2  Load levels are greater than a level 2 Overload 
condition and less than a level 3 Overload condition. 
Alarm 
162 
Output Overload Level 3  Load levels are greater than a level 3 threshold.  Alarm 
168 
UPS On Battery   The UPS is operating from batteries.  Notice 
169 
UPS On Bypass   The UPS is operating from bypass.  Notice 
170 
UPS Off  The UPS is in Standby mode or Fault mode.  Event 
172 
UPS On Command  Indicates a manually requested transition from 
Standby to Operate. This event is not triggered for 
auto restarts.  
Event 
173 
UPS Off Command  A UPS OFF command was received from remote S/W 
and causes the UPS to open up all output relays and 
shed the load. 
Event 
174 
Battery Shutdown  The UPS has shut down due to running on battery for 
a long enough time to exhaust the battery capacity. 
Alarm 
181 
UPS Control Power ON  The UPS is powered up.  Event 
191 
Battery Test Failed  A weak battery string is detected during the battery 
test.  
Notice 
194 
Site Wiring Problem  The difference between ground and neutral voltage is 
less than 30 V. 
Alarm 
199 
Battery Disconnected   Battery voltage is lower than the batteries 
disconnected level defined for this UPS. If ERMs are 
attached, this alarm does not trigger unless the ERMs 
are also disconnected, since they are paralleled with 
the battery bus.   
Alarm 
237 
UPS System Normal  The UPS has started or returned to its normal 
operating mode of operation and no alarms are 
active. 
Event 
1600 
ABM State Charging  The status of ABM charge mode is constant current 
charging. 
Event 
1601 
ABM State Floating  The status of ABM charge mode is floating.  Event 
1602 
ABM State Resting  The status of ABM charge mode is resting.  Event 
1603 
ABM State OFF  The status of ABM charge mode is OFF or disabled.  Event 
1999 
Clock set done  The UPS real time clock setting has been adjusted.  Event