BoostLi Energy Storage Module ESM-48100B1
User Manual
4 Installation and Commissioning
Copyright © Huawei Technologies Co., Ltd.
31
No.
Parameter
Standard Value
3
Equalized charge voltage
53.5 V
4
Float charge voltage
53.4 V
5
Low voltage alarm
47 V
6
Load low voltage disconnection (LLVD)
threshold
46 V
7
Battery low voltage disconnection (BLVD)
threshold
44 V
4.5 Acceptance Criteria
Install and accept the ESM to ensure that the ESM can work properly.
No.
Check Item
Acceptance Criteria
1
Indicator
status
The indicator status is normal (the RUN indicator is steady on and
no indicator is red).
2
Working
status
You are advised to simulate mains disconnection or connection.
The working status of the ESM is normal after the mains
disconnection or connection.
3
Current
The ESM current is normal. According to system settings, the
current deviation is within ±2 A.