FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
5 Parts Replacement
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
166
Figure 5-61 Removing a skylight magnetic lock
Step 4 Install a new skylight magnetic lock and tighten the two screws.
Step 5 Connect cables to the new skylight magnetic lock to the cables cut off in Step 2 using cord
end terminals.
Step 6 Close the rotating skylight. Power on and off the skylight for three consecutive times and
check that the skylight can open properly.
----End
5.5.10 Replacing a Pad Power Connector
Prerequisites
Before installing a pad power connector, prepare the materials listed in Table 5-5.
Table 5-5 Materials
Name
Exterior
Description
Pad power connector
The BOM number is
14190892.
Pad power connector
The BOM number is
14190242.