Category Specications
Air volume ≥ 110 cubic feet per minute (CFM)
Altitude Operating altitude ≤ 3050 m (10006.44 ft)
If the server complies with ASHRAE Class A2, the
maximum operating temperature decreases by 1°C
(1.8°F) for every increase of 300 m (984.25 ft) in
altitude above 900 m (2952.76 ft).
HDDs cannot be used at an altitude of over 3050 m
(10006.44 ft).
Corrosive gaseous
contaminant
Maximum corrosion product thickness growth rate:
Copper corrosion rate test: 300 Å/month (meeting
level G1 requirements of the ANSI/ISA-71.04-2013
standard on gaseous corrosion)
Silver corrosion rate test: 200 Å/month
Particle contaminant The equipment room environment meets the
requirements of ISO 14664-1 Class 8.
There is no explosive, conductive, magnetic, or
corrosive dust in the equipment room.
NOTE
It is recommended that the particulate pollution in the
equipment room be monitored by a professional agency.
Acoustic noise The declared A-weighted sound power levels (LWAd)
and declared average bystander position A-weighted
sound pressure levels (LpAm) listed are measured at
23°C (73.4°F) in accordance with ISO 7779 (ECMA 74)
and reported in accordance with ISO 9296 (ECMA 109).
Idle:
LWAd: 6.7 Bels
LpAm: 52.9 dBA
Operating:
LWAd: 6.9 Bels
LpAm: 55.6 dBA
NOTE
The noise generated during operation varies depending on the
server
conguration, load, and ambient temperature.
Huawei FusionServer Pro 2298 V5 Server
Technical White Paper 6 Product Specications
Issue 05 (2020-09-03) Copyright © Huawei Technologies Co., Ltd. 49