Alarm
ID
Alarm Name Severity Possible Cause Suggestion
2086 External Fan
Abnormal
Major Cause ID = 1–3,
corresponding to FAN 1–3
The external fan is short-
circuited, the power supply
is insucient, or the air
channel is blocked.
1. Turn o the AC and DC
switches, check that
the fan blades are
normal, and clear the
foreign objects around
the fan if there are any.
2. Reinstall the fan and
turn on the AC and DC
switches. If the fault
persists after the device
runs for 15 minutes,
replace the external
fan.
2087 Internal Fan
Abnormal
Major Cause ID = 1–4
The internal fan is short-
circuited, the power supply
is insucient, or the fan is
damaged.
Turn o the AC and DC
switches, wait for 5
minutes, and then turn on
the AC and DC switches. If
the fault persists after the
device runs for 5 minutes,
contact your dealer or
technical support to
replace the device.
2095 Invalid Certicate Warning Cause ID = 1
The digital signature
certicate is invalid.
Check the time or replace
the digital signature
certicate.
2096 Certicate About
to Expire
Warning Cause ID = 1
The digital signature
certicate is about to
expire.
Replace the digital
signature certicate in
time.
2097 Certicate Expired Major Cause ID = 1
The digital signature
certicate has expired.
Replace the digital
signature certicate
immediately.
LUNA2000-200KTL-H0 Smart Power Control System
User Manual 10 Alarm Reference