Alarm
ID
Alarm Name Severity Possible Cause Suggestion
2098 Parallel System
Abnormal
Major Cause ID = 1
The parallel
communication line is
abnormal.
Power o the devices
connected to the same DC
bus (turn o the AC and
DC switches, and wait for
a period specied on the
device safety warning
label), and then perform
the following operations:
Check that the
communications cable is
securely connected and
turn on the AC and DC
switches. If the fault
persists, contact your
dealer or technical
support.
61440 Faulty Monitoring
Unit
Minor Cause ID = 1
1. The ash memory is
insucient.
2. The ash memory has
bad sectors.
Turn o the AC and DC
switches, wait for 5
minutes, and then turn on
the AC and DC switches. If
the fault persists, replace
the monitoring board or
contact your dealer or
technical support.
LUNA2000-200KTL-H0 Smart Power Control System
User Manual 10 Alarm Reference
Issue 05 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 97