EasyManuals Logo

Huawei NetCol5000-A050 Quick Guide

Huawei NetCol5000-A050
31 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
Choose Maint > Wizard Startup to enter
wizard startup.
Open the Service Expert app.
Tap StartUp > Offline Activation on app.
After tapping Yes, the barcode and the
verification code are shown on the screen.
Start
Tap Start on the home screen.
Enter Bar code and Verification code,
and tap Generate PWD.
Enter the generated startup password on
the screen of smart cooling product.
Tap Yes
on Wizard
Startup
screen to
enter
wizard
startup.
Go to step 2.
Refrigerant is
fully charged?
No
Tap No on the Wizard Startup screen to
exit wizard startup.
Charge the remaining amount of
refrigerant from low-pressure needle
valve.
1. First startup flowchart
Tap Enter. The screen turns to Wizard
Startup.
Tap Start on the home screen and choose
Maint > Diagnostic Mode > Enter.
Set the compressor to 3000 rpm.
Choose Maint > Diagnostic Mode > Exit
and tap Shutdown on the home
screen.
Yes
29
2. Wizard startup flowchart
Electric heater
commissioning
Humidifier
commissioning
Cooling system
commissioning
Condensate
pump
commissioning
Indoor fan
commissioning
Commissionin
g interrupted
(Handle the
fault by
referring to
the tips
displayed on
the home
screen.
Perform
wizard startup
after the
handling.)
Start
End
Precautions
Yes
No
Fail
Fail
Fail
Fail
Success
Fail
Select
Commissioning
items
Outdoor fan
commissioning
Success
If a water-cooled module is
installed outdoors, outdoor fan
commissioning is not
implemented.

Other manuals for Huawei NetCol5000-A050

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei NetCol5000-A050 and is the answer not in the manual?

Huawei NetCol5000-A050 Specifications

General IconGeneral
BrandHuawei
ModelNetCol5000-A050
CategoryComputer Hardware
LanguageEnglish

Related product manuals