1. On the home page, tap Shutdown.
2. Turn off the QF1 and QF2. (If there is only one power supply, turn off QF1 only.)
3. (Optional) If the smart cooling product needs to be maintained in power-off mode or
long-term power-off, switch off the smart cooling product circuit breaker on the PDF.
14
(Optional) Power-Off
Ambient
Temperature
Proper Discharge Pressure
Range (Running > Device
Details > Compressor)
Proper Suction Pressure
Range (Running >
Device Details >
Compressor)
Proper Overheating
Degree (Running >
Device Details > EEV)
< 15°C 1.52.5 MPa
0.71.2 MPa 8–15°C
1535°C 1.53.1 MPa
3545°C 2.53.8 MPa
> 45°C 3.14.15 MPa
When the compressor is 3000 rpm, the following table lists the proper system values.
30
Check Item Result
No oil stain exists on the copper pipe thermal insulation foam or bottom
plate.
Passed Failed
The needle valve plug is secured (torque of 0.45±0.05 N•m) , and valve
bonnet is tightened.
Passed Failed
The foreign matter inside the water pan and bottom plate is cleaned up.
Passed Failed
The air filter is correctly installed according to the airflow direction
marked on the frame.
Passed Failed
15
Checking After Commissioning
Appendix A: Precautions Against Adding Glycol
Take antifreezing measures for cooling water pipes if the water-cooled module is configured in low
temperature environments (4
°
C). To prevent glycol solution from corroding pipes, corrosion
inhibitor should be mixed into the glycol solution. For details about the mixing schemes, consult
glycol experts.
Appendix B: Base Drawing
Shock absorption bars (EPDM rubber, 5 mm thick) should be installed between the ground
and the base.
You are advised to use angle steel or channel steel. Thickness of 3 mm to 5 mm is
recommended.
Control the welding process and avoid an excessive error.
The M12 bolts used for securing the cabinet to its base must be at least 80 mm long.
The base bearing capacity must be at least 2 t.
Connect adjacent bases in parallel using bolts. Ensure that each base is secured to the
ground through at least four corners.

Other manuals for Huawei NetCol5000-A050

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei NetCol5000-A050 and is the answer not in the manual?

Huawei NetCol5000-A050 Specifications

General IconGeneral
BrandHuawei
ModelNetCol5000-A050
CategoryComputer Hardware
LanguageEnglish

Related product manuals