3
Refrigerant R410A
2.1
Do not use inferior refrigerant. Otherwise, Huawei has no responsibility for the damage caused
by the inferior refrigerant.
Refrigerant authenticity verification method:
1. Dial the hotline of the refrigerant producer to confirm its reliability.
2. Put the refrigerant indoor for 24 hours. Then use a thermometer to measure the external
surface temperature of the refrigerant cylinder (figure 1) , and connect a pressure gauge to
the cylinder to measure its internal pressure (figure 2) . Look up the following table for the
saturation pressure that corresponds to the external surface temperature, and calculate the
deviation from the internal pressure. If the deviation is more than 0.2 MPa, the refrigerant is
not in good condition. Replace it.
Mapping Between Saturation Temperatures and Pressure of R410A
Saturation
temperature (ºC)
Gauge
(MPa)
Saturation
temperature (ºC)
Gauge
(MPa)
Saturation
temperature (ºC)
Gauge
(MPa)
10 0.99 19 1.31 28 1.69
11 1.02 20 1.35 29 1.74
12 1.05 21 1.39 30 1.79
13 1.09 22 1.43 31 1.84
14 1.12 23 1.47 32 1.89
15 1.16 24 1.51 33 1.94
16 1.19 25
1.56 34
1.99
17 1.23
26
1.60
35
2.05
18
1.27 27
1.65
36
2.10
3
Checking the Nitrogen Pressure
Liquid
pipe
needle
valve
Low-
pressure
needle
valve
Discharge
pipe
needle
valve

Other manuals for Huawei NetCol5000-A050

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei NetCol5000-A050 and is the answer not in the manual?

Huawei NetCol5000-A050 Specifications

General IconGeneral
BrandHuawei
ModelNetCol5000-A050
CategoryComputer Hardware
LanguageEnglish

Related product manuals