Copyright © Huawei Technologies Co., Ltd.
Equipment (excluding ESMs): 300 kg
Single ESM: 60 kg
Ambient temperature: 15°C to 35°C; maximum
charge current: 0.5 C; continuous charge current:
0.5 C
Ambient temperature: 0°C to 35°C; maximum
discharge current: 0.5 C; continuous discharge
current: 0.5 C
Number of battery
modules supported
A single battery cabinet can house eight to
fourteen 48 V/4.8 kWh battery modules
connected in series.
The maximum capacity of a single battery
cabinet is 67.2 kWh. A maximum of eight battery
cabinets can be connected in parallel.