4.3 Determining the Installation Position
4.3.1 Environment Requirements
Basic Requirements
● Do not install the inverter in working or living areas.
● Do not install the inverter in noise-sensitive areas (such as residential areas,
oce areas, and schools) to avoid complaints. If the preceding areas are
unavoidable, the distance between the installation position and noise-
sensitive areas must be greater than 40 m. Alternatively, use other low-noise
models.
● If the device is installed in public places (such as parking lots, stations, and
factories) other than working and living areas, install a protective net outside
the device, set up a safety warning sign to isolate the device, and prevent
unauthorized personnel from approaching the inverter. This is to avoid
personal injury or property loss caused by accidental contact or other reasons
during device operation.
● If the inverter is installed in a place with abundant vegetation, in addition to
routine weeding, harden the ground underneath the inverter using cement or
gravel (the area shall be greater than or equal to 3 m x 2.5 m).