7.1.5.2 Setting Protection Parameters
Procedure
Step 1 Choose Function Menu > Settings > Protect Parameters to go to the parameter
setting screen.
Figure 7-11 Protection parameters (special user)
----End
Parameters
No.
Parameter Description
1 Voltage unbalance protection
threshold (%)
Species the inverter protection threshold when the
power grid voltage is unbalanced.
2 Phase angle oset protection The standards of certain countries and regions require
that the inverter needs to be protected when the
phase angle oset of the power grid three phases
exceeds a certain value.
3 10-min overvoltage protection
threshold (V)
Species the 10-minute overvoltage protection
threshold.
4 10-min overvoltage protection
duration (ms)
Species the 10-minute overvoltage protection
duration.
5 Level-N overvoltage protection
threshold (V)
Species the level-N grid overvoltage protection
threshold.
6 Level-N overvoltage protection
duration (ms)
Species the level-N grid overvoltage protection
duration.
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1)
User Manual 7 Man-Machine Interactions
Issue 19 (2023-12-20) Copyright © Huawei Technologies Co., Ltd. 80