Cable Type Conductor Cross-
Sectional Area
Cable Outer
Diameter
OT/DT
Terminal
Note [1]: For some models, the outer diameter of a single-core cable ranges
from 14 mm to 36 mm based on the label in the maintenance compartment.
Note [2]: For some models, when the OT/DT terminal is crimped as shown in
the following gure and the rubber bae plate of the AC wiring terminal is 112
mm, the maximum conductor cross-sectional area of the single-core cable can
be 400 mm
2
.
Figure 5-9 Specications of the Crimped OT/DT Terminal
Figure 5-10 Specication of the Rubber Bae Plate
NO TE
The cable diameter must comply with local cable standards. The factors that aect
cable selection include the rated current, cable type, routing mode, ambient
temperature, and maximum expected line loss.
When the MBUS is used for communication, it is recommended that the multi-wire
cable be used. The maximum communication distance is 1000 m. If other types of AC
power cables are used, contact Huawei technical support.
Table 5-2 PE cable specications
Conductor Cross-Sectional
Area S of the AC Power Cable
(Unit: mm
2
)
Conductor Cross-Sectional
Area S
P
of the PE Cable
(Unit: mm
2
)
OT/DT
Terminal
S > 35 S
P
≥ S/2 M10
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1)
User Manual 5 Electrical Connections
Issue 19 (2023-12-20) Copyright © Huawei Technologies Co., Ltd. 49