SUN2000-(50KTL-JPM0, 50KTL-JPM1, 63KTL-JPM0)
User Manual
7 Man-Machine Interactions
Copyright © Huawei Technologies Co., Ltd.
75
No.
Parameter
Description
Unit
Default
Value
Value Range
Remarks
12
String
connection
mode
Specifies the
connection mode of
PV strings.
When the PV
strings connect to
the inverter
separately (fully
separate
connection), there
is no need to set
this parameter.
The inverter can
automatically
detect the
connection mode
of the PV strings.
When the PV
strings connect to
one another in
parallel outside the
inverter and then
connect to the
inverter
independently
(fully parallel
connection), set
this parameter to
All PV strings
connected.
N/A
Automatic
detection
Automatic
detection
All PV
strings
separated
All PV
strings
connected
N/A
13
Communic
ation
interrupt
shutdown
The standards of
certain countries and
regions require that
the SUN2000 must
shut down after the
communication is
interrupted for a
certain time.
N/A
Disable
Disable
Enable
If Communication
interrupt shutdown
is set to Enable and
the SUN2000
communication has
been interrupted for
a specified time (set
by Communication
interruption
duration), the
SUN2000 will
automatically shut
down.