Alarm
ID
Alarm
Name
Alarm
Severity
Possible Cause Suggestion
2034 Grid
Overvolt
age
Major Cause ID = 1
The grid voltage exceeds the
upper threshold or the
overvoltage duration exceeds the
time that triggers high voltage
ride-through (HVRT).
1. Check whether the grid
connection voltage
exceeds the upper
threshold. If yes, contact
the local power operator.
2. If you have
conrmed that
the grid connection
voltage exceeds the upper
threshold and have
obtained the consent of
the local power operator,
modify the overvoltage
protection threshold.
3. Check whether the peak
grid voltage exceeds the
upper threshold.
2035 Grid Volt.
Imbalanc
e
Major Cause ID = 1
The dierence between grid
phase voltages exceeds the upper
threshold.
1. Check that the grid
voltage is within the
normal range.
2. Check that the AC output
power cable is correctly
connected. If the AC
output power cable is
correctly connected, yet
the alarm persists and
aects the energy yield of
the PV plant, contact the
local power operator.
SUN2000-(100KTL, 110KTL, 115KTL)-M2
User Manual 8 Maintenance
Issue 02 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 96