Item SUN2000-115KT
L-M2
SUN2000-110KT
L-M2
SUN2000-100KT
L-M2
SUN2000-100KT
L-INM2
Maximum output
current
182.3 A (400 V)
and 151.9 A (480
V)
185.7 A (380 V)
and 176.4 A (400
V)
168.8 A (380 V),
160.4 A (400 V)
and 133.7 A (480
V)
154.6 A (415 V),
133.7 A (480 V)
Power factor 0.8 leading and 0.8 lagging
Maximum total
harmonic
distortion (rated
power)
< 3%
Note a: The rated output voltage is determined by Grid code, which can be set on the SUN2000
app, SmartLogger, or NMS.
Note b: You can determine whether to connect the neutral wire to the SUN2000-115KTL-M2,
SUN2000-110KTL-M2, SUN2000-100KTL-M2, or SUN2000-100KTL-INM2 based on the application
scenario. If no neutral wire is used, set Output mode to Three-phase three-wire. If the neutral
wire is used, set the Output mode to Three-phase four-wire.
Protection
Item
SUN2000-115KTL
-M2
SUN2000-110KTL-
M2
SUN2000-100KTL-
M2
SUN2000-100KT
L-INM2
AFCI - - Supported -
Input DC
switch
Supported
Anti-
islanding
protection
Supported
Output
overcurrent
protection
Supported
Input
reverse
connection
protection
Supported
PV string
fault
detection
Supported
DC surge
protection
Supported
SUN2000-(100KTL, 110KTL, 115KTL)-M2
User Manual 10 Technical Specications
Issue 02 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 112