A cell consists of electrodes and electrolytes, which is the basic unit for the battery. Each cell has a
nominal voltage of 2 V. A battery is a module consisting of single or multiple cells in a shell. Each
battery has a nominal voltage of 2 V or 12 V. The number of cells must be a multiple of 12 (for
example, 180 and 192).
Cell float voltage, Cell equalized volt, Float volt. temp. comp. coef., and EOD voltage threshold
are set for cells.
Advanced Parameters
Set System capacity and Power module capacity according to site specifications. Incorrect
settings may generate an overload alarm, which affects normal UPS running.
Figure 4-35 Advanced Param. screen 1
The rated system capacity equals the capacity of each power module
multiplied by the number of requisite power modules. If this is set
incorrectly, the Module quantity mismatch alarm will be generated.
Power
module
capacity
(kVA)
Rated power module capacity.
Matches the system capacity.
Set in accordance with loading capacity and redundant requirements.
The value can be Normal mode (default), Converter mode, Self-load
mode, or ECO.