UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
The value can be Non-BSC mode (default) or BSC mode (set when the
system is a dual-bus system).
A dual-bus system consists of the master and slave BSC systems. You can
specify the master and slave BSC systems (one master and one slave) and
change the settings under the guidance of maintenance engineers. Set the
master and slave BSC systems to master and slave BSC modes
respectively.
NOTE
Ensure that the BSC signal cable between the master and slave BSC systems is properly
connected and that BSC-related hardware is properly installed.
Figure 4-36 Advanced Param. screen 2
If the customer load is light, set parallel hibernation to alternate modules in
hibernation to prolong their service life as well as improve system
efficiency.
Module
cycle
hiber.
period (d)
A cycle of 1 to 100 days can be set. The parameter is set to 30 days by
default.
High
ambient
temperatu
re alarm
threshold
(°C)
An alarm is generated when the ambient temperature reaches or exceeds the
threshold specified by this parameter.
Low
ambient
temperatu
re alarm
A warning is generated when the ambient temperature is lower than the
parameter value.