UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure 4-56 Basic Parameters 1
Figure 4-57 Basic Parameters 2
A maximum of four CIMs can be connected.
The CIM start address cannot be changed. The DIP switch should be set to
0000 for the first CIM, and the DIP switch setting for a later connected CIM
should increase by 1 (binary) than that set for the previous CIM.
Number of BIMs managed by the CIM.
Number
of battery
strings
Number of battery strings connected in parallel.
Batteries
in a single
battery
Number of batteries in a battery string.