UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
C Alarm List
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
281
Alarm
ID
(Alarm
ID-Caus
e ID)
Alarm
Name
Severit
y
Cause
Solution
for the
power
module is
obstructed
.
0043-1
Fan
abnormal
Critical
The fan
for the
power
module is
abnormal.
The fan
monitorin
g cable
for the
power
module is
not
working
properly.
Replace the faulty power module.
0043-2
The fan is
faulty.
Check the fan or replace the bypass
module.
0043-3
The fan is
faulty.
The fan
monitorin
g cable is
faulty.
1. Replace the fan.
2. Check the fan monitoring cable.
0043-4
0047-1
Not ready
Critical
The ready
switch is
OFF.
Close the ready switch.
0060-4
Inverter
abnormal
Critical
A load
short-circ
uit occurs.
A short
circuit
occurs
inside the
module.
(This fault
seldom
occurs.)
1. Check load cable distributions.
2. If load cable distributions are
normal, replace the power
module.
0061-2
Inverter
alarm
Minor
The I2C
bus is not
1. Rectify the fault and check
whether the alarm is cleared.
2. If the alarm is generated again,