Alarm
ID
(Alarm
ID-Caus
e ID)
normal.
The
E2PROM
is faulty.
replace the power module.
The bypass
waveform is
not normal.
If not all modules generate the
alarm, start the UPS, transfer it
to normal mode, and replace the
faulty module.
If all modules generate the
alarm, open the bypass input
circuit breaker. After the
inverter relay is closed, close
the bypass input circuit breaker
10 seconds later.
The load
is
excessive.
Derating
reduces
the rated
system
power.
The
module is
damaged.
1. Check that there is no overload.
2. Check that the module power is
not derated due to a fan fault.
3. If the alarm persists, replace the
power module.
Load
impact
transfer-to-
bypass
A
large-pow
er RCD
load is
instantly
connected
, or the
output
load
short-circ
uits.
The
inverter
bridge
short-circ
uits.
1. Check the load.
2. If the load is normal, replace the
power module.
1. Check that there is no overload.
2. Check that the module power is
not derated due to a fan fault.