EasyManua.ls Logo

Huawei UPS5000-E-300K-SMT - Page 294

Huawei UPS5000-E-300K-SMT
300 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
C Alarm List
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
285
Alarm
ID
(Alarm
ID-Caus
e ID)
Alarm
Name
Severit
y
Cause
Solution
bypass
UPS is not
normal, and
transfers to
bypass mode.
bypass mode.
0088-1
Rack
address
conflict
Critical
The
configured
rack address
conflicts with
another one.
Check the rack address setting.
0089-1
Rack
output
overload
Minor
The load
is
excessive.
The rack
capacity
setting is
not
appropriat
e.
Check the load and remove
some loads or expand the UPS
power capacity if the UPS is
overloaded.
Check that the configured rack
capacity meets requirements.
0090-1
Dry contact
board fault
Critical
I2C
communicati
on with the
dry contact
board
MUE05A
fails.
Replace the dry contact board
MUE05A.
0090-2
I2C
communicati
on with the
dry contact
board
MUE06A
fails.
Replace the dry contact board
MUE06A.
0356
Battery
Mode
Minor
The UPS is
working in
battery mode.
The running status is displayed. See
details about how to handle other
alarms.
0359
No power
supplied
Warning
No power is
supplied.
The running status is displayed. See
details about how to handle other
alarms.
0332
Output
disabled
Minor
The output is
disabled.
The running status is displayed. See
details about how to handle other
alarms.
0334
BSC
master
Warning
BSC master
system.
The running status is displayed. No
further measures are required.

Table of Contents

Other manuals for Huawei UPS5000-E-300K-SMT

Related product manuals