UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Alarm
ID
(Alarm
ID-Caus
e ID)
The running status is displayed. No
further measures are required.
PDC
bypass
input
breaker
open
The bypass
input circuit
breaker on
the PDC is
OFF.
The running status is displayed. No
further measures are required.
The output
circuit
breaker on
the PDC is
OFF.
1. Check that all UPS output
circuit breakers are ON.
2. On the LCD, check that PDC
output breaker open alarm has
disappeared. If the alarm
persists, tap the Clear Fault
button to clear the alarm.
PDC
Maint.
breaker
closed
The
maintenance
circuit
breaker on
the PDC is
ON.
The running status is displayed. No
further measures are required.
The mains
input circuit
breaker is
OFF.
The running status is displayed. No
further measures are required.
The bypass
input circuit
breaker is
OFF.
The running status is displayed. No
further measures are required.
The
maintenance
circuit
breaker is
ON.
The running status is displayed. No
further measures are required.
The generator
is connected.
The running status is displayed. No
further measures are required.
Insufficient
redundant
racks
The load
is
excessive.
The
configure
d number
1. Reduce the load.
2. Decrease the configured number
of redundant racks.